Description:
COOLER UNIT,AIR

Detail:
A UNIT COMPRISING A FIN AND TUBE HEAT TRANSFER ELEMENT, FILTERS AND MAY OR MAY NOT HAVE A MOTOR DRIVEN FAN, INCLOSED IN A CASING FOR THE PURPOSE OF COOLING AND REMOVING MOISTURE FROM THE AIR IN A SPACE WHERE THE UNIT IS INSTALLED. IT MAY INCLUDE ELECTRIC HEATER AND/OR ELECTROSTATIC PRECIPITATOR. EXCLUDES UNITS CONTAINING COMPRESSOR, CONDENSER AND MEANS FOR INTRODUCING AIR FROM OUTSIDE SOURCES.


Manufacturer Information:
FCU V7-LVP-9.0KW38450ENGINEERED COIL COMPANY
FCU-V7-9.0KW-LVP38450ENGINEERED COIL COMPANY
V-7 LVP-9.0KW38450ENGINEERED COIL COMPANY


Techincal Specification:
CASE WITH BUILT-IN CONDENSATE DRAIN PANINCLUDED
COIL TUBE QUANTITY1
CONNECTION TYPEFLANGE UNION
COOLING MEDIUMCHILLED WATER
CURRENT TYPEAC FAN MOTOR
CURRENT TYPEAC HEATER
FAN DRIVE TYPEDIRECT
FAN TYPECENTRIFUGAL
FREQUENCY IN HERTZ60.0 HEATER
FREQUENCY IN HERTZ60.0 FAN MOTOR
HEATER WATTAGE RATING IN KILOWATTS9.0
OVERALL DEPTH52.000 INCHES NOMINAL
OVERALL HEIGHT19.000 INCHES NOMINAL
OVERALL WIDTH52.000 INCHES NOMINAL
MATERIALCOPPER TUBE
MATERIALSTEEL CASE
NOMINAL CAPACITY IN BTU PER HOUR45560.0 COOLING AND 45560.0 HEATING
OPERATING SPEED AT RATED CAPACITY IN RPM1800.0
PHASETHREE FAN MOTOR
PHASETHREE HEATER
PRIME MOVER HORSEPOWER RATING0.750
RETURN CONNECTION SIZE.625 IN OD
SPECIAL FEATURESMIL-A-24775; REVERSABLE CONNECTIONS (LH/RH), HIGH IMPACT SHOCK AND VIBRATION RESISTANCE; HAS LVP (LOW VOLTAGE PROTECTION) CAPABILITY
SUPPLY CONNECTION SIZE.625 IN OD
TUBE CIRCUIT QUANTITY32
VOLTAGE IN VOLTS440.0 FAN MOTOR
VOLTAGE IN VOLTS440.0 HEATER