5925-00-227-0386 CIRCUIT BREAKER Index 5925-00-227-0390 CIRCUIT BREAKER

National Stock Number:
5925-00-227-0387

Federal Supply Class:
5925

National Item Identification Number:
002270387

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
153219265054WESTINGHOUSE ELECTRIC CORP POWER GENERATION-GENERATOR DIV
153219279500WESTINGHOUSE ELECTRIC CORP
C218293-106845RAYTHEON COMPANY
172083479500WESTINGHOUSE ELECTRIC CORP


Techincal Specification:
POLE QUANTITY1
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE15.0 AMPERES AC AND
15.0 AMPERES DC SINGLE LOCATION
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
TERMINAL TYPE AND QUANTITY2 THREADED STUD
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS125.0 AC AND
32.0 DC SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
RESET METHODMANUAL
BODY STYLESINGLE POLE TYPE
MOUNTING FACILITY TYPE AND QUANTITY2 THREADED HOLE
CASE MATERIALPLASTIC
TRIP RELEASE METHODTHERMAL SINGLE LOCATION
FREQUENCY IN HERTZ60.0 SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS5000.0 AC AND
5000.0 DC SINGLE LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
TRIP RELEASE AMBIENT TEMP RATING25.0 DEG CELSIUS NOMINAL SINGLE LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT12.800 MINIMUM AT 200 PCT AND
38.000 MAXIMUM AT 200 PCT SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT122.0 SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BODY LENGTH2.985 INCHES MINIMUM AND
3.016 INCHES MAXIMUM
BODY WIDTH1.000 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.796 INCHES MINIMUM AND
1.828 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.625 INCHES NOMINAL
BOSS HEIGHT0.005 INCHES NOMINAL
MOUNTING SURFACE TO TERMINAL END DISTANCE2.554 INCHES MINIMUM AND
2.624 INCHES MAXIMUM
THREAD SERIES DESIGNATORUNC
NOMINAL THREAD SIZE0.164 INCHES
THREAD QUANTITY PER INCH32
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDGENERAL PURPOSE
ARC QUENCHING METHODDEION
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
PRECIOUS MATERIALSILVER
PRECIOUS MATERIAL AND LOCATIONCONTACT SURFACES SILVER
FRAGILITY FACTORMODERATELY RUGGED


Click here to Register for Free 30-day Trial