5925-00-234-0121 CIRCUIT BREAKER Index 5945-00-234-0123 CHOPPER,ELECTRONIC

National Stock Number:
5925-00-234-0122

Federal Supply Class:
5925

National Item Identification Number:
002340122

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
247ASC0682-00230003NAVAL AIR SYSTEMS COMMAND MANAGED ORIGINAL DESIGN ACTIVITY NOT MATERIAL/PARTS SUPPLIER
RRP401-880-281541SENSATA TECHNOLOGIES MARYLAND, INC


Techincal Specification:
BODY STYLERECTANGULAR DIMENSIONAL ENVELOPE
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FREQUENCY IN HERTZ400.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDHERMETICALLY SEALED
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
OVERALL HEIGHT1.515 INCHES MAXIMUM
OVERALL LENGTH2.850 INCHES MAXIMUM
OVERALL WIDTH1.890 INCHES MAXIMUM
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE22.0 AMPERES AC FIRST LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE22.0 AMPERES AC SECOND LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE33.0 AMPERES DC THIRD LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS500.0 DC THIRD LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS300.0 AC FIRST LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS300.0 AC SECOND LOCATION
MOUNTING FACILITY TYPE AND QUANTITY4 THREADED STUD
NOMINAL THREAD SIZE0.138 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS12.0 DC THIRD LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC FIRST LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC SECOND LOCATION
POLE QUANTITY3
RESET METHODAUTOMATIC
SPECIAL FEATURESSUPPLIED WITH EXTERNALLY MTD RESISTOR LOCATED BETWEEN POLE 2 TERM.
TERMINAL TYPE AND QUANTITY6 WIRE HOOK
THREAD SERIES DESIGNATORUNC
THREAD QUANTITY PER INCH32
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.055 MINIMUM AT 200 PCT AND 0.095 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS