5925-00-248-1398 TRIPPER,CIRCUIT BREAKER Index 5925-00-248-1401 TRIPPER,CIRCUIT BREAKER

National Stock Number:
5925-00-248-1399

Federal Supply Class:
5925

National Item Identification Number:
002481399

Description:
TRIPPER,CIRCUIT BREAKER

Detail:
AN ELECTROMECHANICAL DEVICE WHICH RELEASES THE HOLDING MECHANISM AND PERMITS THE CONTACTS OF A CIRCUIT BREAKER TO OPEN. IT IS A REPLACEMENT PART OF A CIRCUIT BREAKER. DOES NOT INCLUDE RELAYS. SEE ALSO THERMAL RELEASE, CIRCUIT BREAKER.


Manufacturer Information:
176477179500WESTINGHOUSE ELECTRIC CORP
S-176477111660WESTINGHOUSE ELECTRIC CORP CONTROL BUSINESS UNIT


Techincal Specification:
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS+1800.0 TO 2100.0 AC AND +1800.0 TO 2100.0 DC ALL LOCATIONS
BODY STYLERECTANGULAR DIMENSIONAL ENVELOPE
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FEATURES PROVIDEDADJUSTABLE TRIP RELEASE
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE300.0 AMPERES AC AND 300.0 AMPERES DC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY6 TERMINAL
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS500.0 AC AND 250.0 DC ALL LOCATIONS
OVERALL HEIGHT4.250 INCHES NOMINAL
OVERALL LENGTH7.750 INCHES NOMINAL
OVERALL WIDTH4.750 INCHES NOMINAL
POLE QUANTITY3
TERMINAL TYPE AND QUANTITY6 SCREW
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT5400.000 NOMINAL AT 150 PCT AND 600.000 MINIMUM AT 200 PCT AND 1440.000 MAXIMUM AT 200 PCT AND 120.000 MINIMUM AT 300 PCT AND 450.000 MAXIMUM AT 300 PCT ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING50.0 CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND TIME DELAY ALL LOCATIONS
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT200.0 ALL LOCATIONS