5925-00-259-2093 CIRCUIT BREAKER Index 5925-00-259-2098 CIRCUIT BREAKER

National Stock Number:
5925-00-259-2096

Federal Supply Class:
5925

National Item Identification Number:
002592096

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
0411TSHX2574193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
204066-00012436BAE SYSTEMS INFORMATION AND ELECTRONIC SYSTEMS INTEGRATION INC.
204066-00014100STROMBERG-CARLSON CORP A PLESSEY TELECOMMUNICATIONS CO
206292-79962989XY RESOURCES INC DBA TELECOM INSTALLATION DIV


Techincal Specification:
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.750 INCHES NOMINAL
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
ARC QUENCHING METHODMAGNETIC BLOWOUT
AUXILIARY SWITCH FUNCTION AND QUANTITY1 ALARM
BODY HEIGHT2.830 INCHES NOMINAL
BODY LENGTH4.750 INCHES NOMINAL
BODY STYLESINGLE POLE TYPE
BODY WIDTH1.030 INCHES NOMINAL
CASE MATERIALPLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH4.3880 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE25.0 AMPERES DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS5000.0 DC SINGLE LOCATION
III FRAGILITY FACTORMODERATELY RUGGED
III SPECIAL HANDLING FEATUREMAGNETIC
III UNPACKAGED UNIT WEIGHT0.688 POUNDS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF
POLE QUANTITY1
PROPRIETARY CHARACTERISTICSPACS
MOUNTING FACILITY TYPE AND QUANTITY2 THREADED HOLE
NOMINAL THREAD SIZE0.138 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS50.0 DC SINGLE LOCATION
RESET METHODAUTOMATIC
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE ONE
SWITCH TERMINAL TYPEPIN
SWITCH VOLTAGE RATING AND TYPE IN VOLTS125.0 AC AND 50.0 DC
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS5.0 AC AND 1.0 DC
TERMINAL TYPE AND QUANTITY1 COMPRESSION AND 1 TAB W/SCREW
THREAD QUANTITY PER INCH32
THREAD SERIES DESIGNATORUNC
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.180 MINIMUM AT 200 PCT SINGLE LOCATION AND 3.000 MAXIMUM AT 200 PCT SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODMAGNETIC-HYDRAULIC SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 SINGLE LOCATION


Click here to Register for Free 30-day Trial