2530-00-383-9706 KNUCKLE Index 5310-00-383-9712 WASHER,KEY

National Stock Number:
5925-00-383-9707

Federal Supply Class:
5925

National Item Identification Number:
003839707

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
2263SHK-60-115VAC-374193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
351-590-00807421L3HARRIS INTERSTATE ELECTRONICS CORPORATION


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONBETWEEN POLE ONE AND TWO
ARC QUENCHING METHODAIR
AUXILIARY SWITCH FUNCTION AND QUANTITY1 ALARM
BODY HEIGHT2.688 INCHES NOMINAL
BODY LENGTH5.250 INCHES NOMINAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH2.000 INCHES NOMINAL
BOSS HEIGHT0.219 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.984 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH4.359 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH3.062 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.984 INCHES NOMINAL
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS115.0 AC AND 250.0 DC ALL LOCATIONS
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE60.0 AMPERES AC AND 60.0 AMPERES DC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS5000.0 AC AND 5000.0 DC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 THREADED HOLE
NOMINAL THREAD SIZE0.138 INCHES
POLE QUANTITY2
RESET METHODMANUAL
SPECIAL HANDLING FEATUREMAGNETIC
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE TWO
TERMINAL TYPE AND QUANTITY4 THREADED STUD
THREAD QUANTITY PER INCH32
THREAD SERIES DESIGNATORUNC
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.350 MINIMUM AT 200 PCT AND 3.500 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS


Click here to Register for Free 30-day Trial