POLE QUANTITY | 4 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 5.0 AMPERES AC FIRST LOCATION |
| 5.0 AMPERES AC SECOND LOCATION |
| 5.0 AMPERES AC THIRD LOCATION |
| 300.0 MILLIAMPERES DC FOURTH LOCATION |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
TERMINAL TYPE AND QUANTITY | 8 THREADED STUD |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC FIRST LOCATION |
| 250.0 AC SECOND LOCATION |
| 250.0 AC THIRD LOCATION |
| 50.0 DC FOURTH LOCATION |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND |
| TIME DELAY ALL LOCATIONS |
RESET METHOD | MANUAL |
BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
MOUNTING FACILITY TYPE AND QUANTITY | 8 THREADED HOLE |
CASE MATERIAL | PLASTIC |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
FREQUENCY IN HERTZ | 60.0 FIRST LOCATION |
| 60.0 SECOND LOCATION |
| 60.0 THIRD LOCATION |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC FIRST LOCATION |
| 1000.0 AC SECOND LOCATION |
| 1000.0 AC THIRD LOCATION |
| 2000.0 DC FOURTH LOCATION |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP FIRST LOCATION |
| SERIES TRIP SECOND LOCATION |
| SERIES TRIP THIRD LOCATION |
| RELAY TRIP FOURTH LOCATION |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.500 MINIMUM AT 200 PCT AND |
| 7.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
BODY LENGTH | 2.490 INCHES MINIMUM AND |
| 2.510 INCHES MAXIMUM |
BODY WIDTH | 2.990 INCHES MINIMUM AND |
| 3.010 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.928 INCHES MINIMUM AND |
| 1.948 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.740 INCHES MINIMUM AND |
| 0.760 INCHES MAXIMUM |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.052 INCHES MINIMUM AND |
| 2.072 INCHES MAXIMUM |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.740 INCHES MINIMUM AND |
| 0.760 INCHES MAXIMUM |
BOSS HEIGHT | 0.130 INCHES MINIMUM AND |
| 0.150 INCHES MAXIMUM |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.461 INCHES MINIMUM AND |
| 2.481 INCHES MAXIMUM |
THREAD SERIES DESIGNATOR | UNC |
NOMINAL THREAD SIZE | 0.138 INCHES |
THREAD QUANTITY PER INCH | 32 |
MANUAL ACTUATOR TYPE AND QUANTITY | 4 TOGGLE |
ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, THREE, AND FOUR LINKED |
AUXILIARY SWITCH FUNCTION AND QUANTITY | 3 ALARM |
SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE AND |
| INTERNAL AT POLE TWO AND |
| INTERNAL AT POLE THREE |
SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
SWITCH CURRENT RATING AND TYPE IN AMPS | 2.5 AC AND |
| 1.0 DC |
SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC AND |
| 50.0 DC |
SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | MOISTURE RESISTANT AND |
| FUNGUS RESISTANT |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
SPECIAL HANDLING FEATURE | MAGNETIC |
FRAGILITY FACTOR | MODERATELY RUGGED |