5970-00-601-2440 INSULATOR,PLATE Index 4810-00-601-2448 VALVE,SOLENOID

National Stock Number:
5925-00-601-2445

Federal Supply Class:
5925

National Item Identification Number:
006012445

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
32A7771G6779500WESTINGHOUSE ELECTRIC CORP
32A7771G6789946EATON CORPORATION
N218829-106845RAYTHEON COMPANY


Techincal Specification:
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH8.120 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH2.750 INCHES NOMINAL
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
BODY HEIGHT4.080 INCHES NOMINAL
BODY LENGTH10.120 INCHES NOMINAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH8.250 INCHES NOMINAL
BOSS HEIGHT0.250 INCHES NOMINAL
CASE MATERIALPLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH7.250 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH2.750 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE150.0 AMPERES AC ALL LOCATIONS AND 150.0 AMPERES DC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS15000.0 AC ALL LOCATIONS AND 25000.0 DC ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT
POLE QUANTITY3
PRECIOUS MATERIAL AND LOCATIONCONTACT SURFACES SILVER
PRECIOUS MATERIALSILVER
PROPRIETARY CHARACTERISTICSPACS
MOUNTING FACILITY TYPE AND QUANTITY6 THREADED HOLE AND 4 UNTHREADED HOLE
NOMINAL THREAD SIZE0.625 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS
RESET METHODMANUAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY6 SCREW
THREAD QUANTITY PER INCH32
THREAD SERIES DESIGNATORUNF
TRIP RELEASE AMBIENT TEMP RATING25.0 DEG CELSIUS MAXIMUM ALL LOCATIONS
TRIP RELEASE CHARACTERISTICINSTANTANEOUS ALL LOCATIONS
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT120.0 ALL LOCATIONS
UNTHREADED MOUNTING HOLE DIAMETER0.312 INCHES NOMINAL