5925-00-620-5844 CIRCUIT BREAKER Index 5925-00-620-5852 CIRCUIT BREAKER

National Stock Number:
5925-00-620-5851

Federal Supply Class:
5925

National Item Identification Number:
006205851

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
6319452G14L24446GENERAL ELECTRIC COMPANY
6319452G14L71669GENERAL ELECTRIC CO SWITCHGEAR AND CONTROL DIVISION OF APPARATUS GROUP
6319482G3L03497GENERAL ELECTRIC CO OUTDOOR BREAKER BUSINESS SECTION
DMS 79009B16236DLA LAND AND MARITIME DBA ENGINEERING AND TECHNICAL SUPPORT DIV DOCUMENT STANDARDIZATION DIVISION (VENDOR ITEM DRAWINGS)
6319482G3L24446GENERAL ELECTRIC COMPANY
6319482G1371669GENERAL ELECTRIC CO SWITCHGEAR AND CONTROL DIVISION OF APPARATUS GROUP
TN231125-125AMP24446GENERAL ELECTRIC COMPANY
TN231125-125AMP60969GENERAL ELECTRIC CO ELECTRICAL DISTRIBUTION AND CONTROL
TN23112560969GENERAL ELECTRIC CO ELECTRICAL DISTRIBUTION AND CONTROL
TN231125-125AMP71669GENERAL ELECTRIC CO SWITCHGEAR AND CONTROL DIVISION OF APPARATUS GROUP


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE125.0 AMPERES AC AND 125.0 AMPERES DC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS10000.0 AC AND 5000.0 DC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY2 THREADED HOLE
NOMINAL THREAD SIZE0.250 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS125.0 AC AND 125.0 DC ALL LOCATIONS
POLE QUANTITY3
RESET METHODMANUAL
THREAD SERIES DESIGNATORUNC
THREAD QUANTITY PER INCH20
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT10.000 MINIMUM AT 200 PCT AND 210.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING50.0 CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND TIME DELAY ALL LOCATIONS
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT115.0 ALL LOCATIONS