ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
BODY LENGTH | 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM |
BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
BODY WIDTH | 2.240 INCHES MINIMUM AND 2.260 INCHES MAXIMUM |
BOSS HEIGHT | 0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
FRAGILITY FACTOR | MODERATELY RUGGED |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT AND EXPLOSION RESISTANT |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MATERIAL | PLASTIC CASE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 45.0 AMPERES AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.689 INCHES MINIMUM AND 2.813 INCHES MAXIMUM |
NOMINAL THREAD SIZE | 0.138 INCHES |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 208.0 AC ALL LOCATIONS |
POLE QUANTITY | 3 |
RESET METHOD | MANUAL |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
TERMINAL TYPE AND QUANTITY | 3 SCREW |
THREAD SERIES DESIGNATOR | UNC |
THREAD QUANTITY PER INCH | 32 |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 10.000 MINIMUM AT 150 PCT AND 30.000 MAXIMUM AT 150 PCT AND 4.000 MINIMUM AT 200 PCT AND 10.000 MAXIMUM AT 200 PCT AND 1.400 MINIMUM AT 300 PCT AND 4.000 MAXIMUM AT 300 PCT ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
ULTIMATE TRIP TIME PER POLE IN SECONDS | 18.000 MINIMUM AND 70.000 MAXIMUM ALL LOCATIONS |