6105-00-823-2505 MOTOR-TACHOMETER GENERATOR Index 5995-00-823-2520 CABLE ASSEMBLY,SPECIAL PURPOSE,E

National Stock Number:
5925-00-823-2509

Federal Supply Class:
5925

National Item Identification Number:
008232509

Description:
TRIPPER,CIRCUIT BREAKER

Detail:
AN ELECTROMECHANICAL DEVICE WHICH RELEASES THE HOLDING MECHANISM AND PERMITS THE CONTACTS OF A CIRCUIT BREAKER TO OPEN. IT IS A REPLACEMENT PART OF A CIRCUIT BREAKER. DOES NOT INCLUDE RELAYS. SEE ALSO THERMAL RELEASE, CIRCUIT BREAKER.


Manufacturer Information:
HLA3225T89946EATON CORPORATION
S370D749G2889946EATON CORPORATION
S455D563G2889946EATON CORPORATION


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
BODY STYLERECTANGULAR DIMENSIONAL ENVELOPE
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
OVERALL HEIGHT4.062 INCHES NOMINAL
OVERALL LENGTH13.094 INCHES NOMINAL
OVERALL WIDTH8.250 INCHES NOMINAL
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE225.0 AMPERES AC AND 225.0 AMPERES DC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 UNTHREADED HOLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS600.0 AC AND 250.0 DC ALL LOCATIONS
POLE QUANTITY3
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY6 COMPRESSION
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND TIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT93.000 MINIMUM AT 200 PCT AND 550.000 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
UNTHREADED MOUNTING HOLE DIAMETER0.312 INCHES NOMINAL


Click here to Register for Free 30-day Trial