3110-00-864-9404 BEARING,ROLLER,CYLINDRICAL Index 5905-00-864-9407 RESISTOR,FIXED,WIREWOUND,INDUCT

National Stock Number:
5925-00-864-9405

Federal Supply Class:
5925

National Item Identification Number:
008649405

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
613415-898897LOCKHEED MARTIN CORP
74-648-50-674193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
MS25305-5096906MILITARY STANDARDS PROMULGATED BY MILITARY DEPARTMENTS UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M


Techincal Specification:
POLE QUANTITY3
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE50.0 AMPERES AC ALL LOCATIONS
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
TERMINAL TYPE AND QUANTITY6 THREADED STUD
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS208.0 AC ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
RESET METHODMANUAL
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
MOUNTING FACILITY TYPE AND QUANTITY6 UNTHREADED HOLE
CASE MATERIALPLASTIC
UNPACKAGED UNIT WEIGHT0.810 POUNDS NOMINAL
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONS
FREQUENCY IN HERTZ400.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS3500.0 AC ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.300 MINIMUM AT 200 PCT AND
0.900 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BODY LENGTH2.500 INCHES NOMINAL
BODY WIDTH2.273 INCHES NOMINAL
BODY HEIGHT2.000 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.190 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.750 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH1.812 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.750 INCHES NOMINAL
MOUNTING SURFACE TO TERMINAL END DISTANCE1.990 INCHES MINIMUM AND
2.010 INCHES MAXIMUM
NOMINAL THREAD SIZE0.138 INCHES
UNTHREADED MOUNTING HOLE DIAMETER0.562 INCHES NOMINAL
MANUAL ACTUATOR TYPE AND QUANTITY3 TOGGLE
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDHUMIDITY RESISTANT AND
VIBRATION RESISTANT AND
SHOCK RESISTANT AND
EXPLOSION PROOF AND
SALT SPRAY PROOF AND
FUNGUS RESISTANT AND
SAND RESISTANT AND
DUSTPROOF
ARC QUENCHING METHODMAGNETIC BLOWOUT
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SPECIAL HANDLING FEATUREMAGNETIC
FRAGILITY FACTORMODERATELY RUGGED


Click here to Register for Free 30-day Trial