5905-00-865-9617 RESISTOR,VARIABLE,WIRE WOUND,NON Index 5925-00-865-9619 CIRCUIT BREAKER

National Stock Number:
5925-00-865-9618

Federal Supply Class:
5925

National Item Identification Number:
008659618

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
NEF21202002201CHALLENGER ACQUISITION CORP ENGINEERED DISTRIBUTION PRODUCTS DIV
NEF21202021810CHALLENGER ELECTRICAL EQUIPMENT CORP
NEF21302021810CHALLENGER ELECTRICAL EQUIPMENT CORP
NEF21402021810CHALLENGER ELECTRICAL EQUIPMENT CORP


Techincal Specification:
POLE QUANTITY1
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE20.0 AMPERES AC AND
20.0 AMPERES DC SINGLE LOCATION
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
TERMINAL TYPE AND QUANTITY2 COMPRESSION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS277.0 AC AND
125.0 DC SINGLE LOCATION
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND
TIME DELAY SINGLE LOCATION
RESET METHODMANUAL
BODY STYLESINGLE POLE TYPE
MOUNTING FACILITY TYPE AND QUANTITY4 SLOT
CASE MATERIALPLASTIC
TRIP RELEASE METHODTHERMAL-MAGNETIC SINGLE LOCATION
FREQUENCY IN HERTZ60.0 SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS14000.0 AC AND
10000.0 DC SINGLE LOCATION
TRIP RELEASE AMBIENT TEMP RATING40.0 DEG CELSIUS NOMINAL SINGLE LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT24.000 MINIMUM AT 200 PCT AND
65.000 MAXIMUM AT 200 PCT SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT140.0 SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BODY LENGTH6.219 INCHES NOMINAL
BODY WIDTH1.375 INCHES NOMINAL
BODY HEIGHT3.406 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH5.125 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH5.219 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH1.125 INCHES NOMINAL
BOSS HEIGHT0.203 INCHES NOMINAL
MOUNTING SLOT WIDTH0.250 INCHES NOMINAL
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDGENERAL PURPOSE
ARC QUENCHING METHODMAGNETIC BLOWOUT
STORAGE TYPEGENERAL PURPOSE WAREHOUSE


Click here to Register for Free 30-day Trial