POLE QUANTITY | 1 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC AND |
| 20.0 AMPERES DC SINGLE LOCATION |
CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
TERMINAL TYPE AND QUANTITY | 2 COMPRESSION |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 277.0 AC AND |
| 125.0 DC SINGLE LOCATION |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND |
| TIME DELAY SINGLE LOCATION |
RESET METHOD | MANUAL |
BODY STYLE | SINGLE POLE TYPE |
MOUNTING FACILITY TYPE AND QUANTITY | 4 SLOT |
CASE MATERIAL | PLASTIC |
TRIP RELEASE METHOD | THERMAL-MAGNETIC SINGLE LOCATION |
FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 14000.0 AC AND |
| 10000.0 DC SINGLE LOCATION |
TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL SINGLE LOCATION |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 24.000 MINIMUM AT 200 PCT AND |
| 65.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 140.0 SINGLE LOCATION |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
BODY LENGTH | 6.219 INCHES NOMINAL |
BODY WIDTH | 1.375 INCHES NOMINAL |
BODY HEIGHT | 3.406 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.125 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 5.219 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.125 INCHES NOMINAL |
BOSS HEIGHT | 0.203 INCHES NOMINAL |
MOUNTING SLOT WIDTH | 0.250 INCHES NOMINAL |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE ONE |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |