5925-00-929-7271 CIRCUIT BREAKER Index 5925-00-929-7273 CIRCUIT BREAKER

National Stock Number:
5925-00-929-7272

Federal Supply Class:
5925

National Item Identification Number:
009297272

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
AM17-10-115-200VAC54-400CY74193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
DMS 83059B16236DLA LAND AND MARITIME DBA ENGINEERING AND TECHNICAL SUPPORT DIV DOCUMENT STANDARDIZATION DIVISION (VENDOR ITEM DRAWINGS)
MIL-C-580981349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
MS25304-1096906MILITARY STANDARDS PROMULGATED BY MILITARY DEPARTMENTS UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M


Techincal Specification:
POLE QUANTITY1
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE10.0 AMPERES AC AND
10.0 AMPERES DC SINGLE LOCATION
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
TERMINAL TYPE AND QUANTITY2 SCREW
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS120.0 AC AND
30.0 DC SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
RESET METHODMANUAL
BODY STYLESINGLE POLE TYPE
MOUNTING FACILITY TYPE AND QUANTITY2 THREADED HOLE
CASE MATERIALPLASTIC
TRIP RELEASE METHODTHERMAL SINGLE LOCATION
FREQUENCY IN HERTZ400.0 SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS3500.0 AC AND
3000.0 DC SINGLE LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
TRIP RELEASE AMBIENT TEMP RATING25.0 DEG CELSIUS NOMINAL SINGLE LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT18.000 MINIMUM AT 200 PCT AND
80.000 MAXIMUM AT 200 PCT SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0 SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BODY LENGTH2.500 INCHES NOMINAL
BODY WIDTH0.750 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.190 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH1.812 INCHES NOMINAL
MOUNTING SURFACE TO TERMINAL END DISTANCE2.000 INCHES NOMINAL
THREAD SERIES DESIGNATORUNC
NOMINAL THREAD SIZE0.138 INCHES
THREAD QUANTITY PER INCH32
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDEXPLOSION RESISTANT AND
MOISTURE RESISTANT
TEST DATA DOCUMENT81349-MIL-C-5809 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.).
ARC QUENCHING METHODMAGNETIC BLOWOUT
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SPECIAL HANDLING FEATUREMAGNETIC
FRAGILITY FACTORMODERATELY RUGGED
SPECIFICATION/STANDARD DATA96906-MS25304 GOVERNMENT STANDARD
SPEC/STD CONTROLLING DATA
MANUFACTURERS CODE81349
NON-DEFINITIVE GOVERNMENT SPEC/STD REFERENCEMIL-C-5809
MANUFACTURERS CODE96906
DEFINITIVE GOVERNMENT SPEC/STD REFERENCEMS25304-10