5925-00-934-2789 CIRCUIT BREAKER Index 5925-00-934-2791 CIRCUIT BREAKER

National Stock Number:
5925-00-934-2790

Federal Supply Class:
5925

National Item Identification Number:
009342790

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
TED134C5090WL03497GENERAL ELECTRIC CO OUTDOOR BREAKER BUSINESS SECTION
TEF134C5090WL03497GENERAL ELECTRIC CO OUTDOOR BREAKER BUSINESS SECTION


Techincal Specification:
POLE QUANTITY3
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE90.0 AMPERES AC ALL LOCATIONS
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
TERMINAL TYPE AND QUANTITY6 COMPRESSION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS480.0 AC ALL LOCATIONS
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND
TIME DELAY ALL LOCATIONS
RESET METHODMANUAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
MOUNTING FACILITY TYPE AND QUANTITY6 UNTHREADED HOLE
CASE MATERIALPLASTIC
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS15000.0 AC ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING50.0 DEG CELSIUS NOMINAL ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.050 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT135.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BODY LENGTH6.310 INCHES NOMINAL
BODY WIDTH4.125 INCHES NOMINAL
BODY HEIGHT3.380 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH5.250 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH1.375 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH4.880 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH1.375 INCHES NOMINAL
BOSS HEIGHT0.188 INCHES NOMINAL
UNTHREADED MOUNTING HOLE DIAMETER0.190 INCHES NOMINAL
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
FRAGILITY FACTORMODERATELY RUGGED


Click here to Register for Free 30-day Trial