5925-00-948-0042 TRIPPER,CIRCUIT BREAKER Index 5925-00-948-0044 TRIPPER,CIRCUIT BREAKER

National Stock Number:
5925-00-948-0043

Federal Supply Class:
5925

National Item Identification Number:
009480043

Description:
TRIPPER,CIRCUIT BREAKER

Detail:
AN ELECTROMECHANICAL DEVICE WHICH RELEASES THE HOLDING MECHANISM AND PERMITS THE CONTACTS OF A CIRCUIT BREAKER TO OPEN. IT IS A REPLACEMENT PART OF A CIRCUIT BREAKER. DOES NOT INCLUDE RELAYS. SEE ALSO THERMAL RELEASE, CIRCUIT BREAKER.


Manufacturer Information:
2602D83G2011660WESTINGHOUSE ELECTRIC CORP CONTROL BUSINESS UNIT
657D789G2011660WESTINGHOUSE ELECTRIC CORP CONTROL BUSINESS UNIT
HKA3125T11660WESTINGHOUSE ELECTRIC CORP CONTROL BUSINESS UNIT
KA3125T11660WESTINGHOUSE ELECTRIC CORP CONTROL BUSINESS UNIT
S459D984G2011660WESTINGHOUSE ELECTRIC CORP CONTROL BUSINESS UNIT
S657D789G2011660WESTINGHOUSE ELECTRIC CORP CONTROL BUSINESS UNIT
S657D789G2065054WESTINGHOUSE ELECTRIC CORP POWER GENERATION-GENERATOR DIV


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS+625.0 TO 1250.0 AC ALL LOCATIONS
BODY STYLERECTANGULAR DIMENSIONAL ENVELOPE
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FEATURES PROVIDEDADJUSTABLE TRIP RELEASE
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
OVERALL HEIGHT3.812 INCHES NOMINAL
OVERALL LENGTH10.500 INCHES NOMINAL
OVERALL WIDTH5.000 INCHES NOMINAL
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE125.0 AMPERES AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 UNTHREADED HOLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS600.0 AC ALL LOCATIONS
POLE QUANTITY3
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY6 COMPRESSION
TRIP RELEASE AMBIENT TEMP RATING40.0 CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT160.000 MINIMUM AT 200 PCT AND 360.000 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT140.0 ALL LOCATIONS
UNTHREADED MOUNTING HOLE DIAMETER0.250 INCHES NOMINAL