ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE ONE |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | MOISTURE RESISTANT AND FUNGUS RESISTANT |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC AND 125.0 DC ALL LOCATIONS |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 90.0 AMPERES AC AND 90.0 AMPERES DC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 7500.0 AC AND 7500.0 DC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 6 UNTHREADED HOLE |
POLE QUANTITY | 3 |
RESET METHOD | MANUAL |
TERMINAL TYPE AND QUANTITY | 6 SCREW |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 300.000 MINIMUM AT 125 PCT AND 7200.000 MAXIMUM AT 125 PCT AND 2800.000 MINIMUM AT 200 PCT AND 110.000 MAXIMUM AT 200 PCT AND 6.000 MINIMUM AT 300 PCT AND 23.000 MAXIMUM AT 300 PCT AND 2.000 MINIMUM AT 400 PCT AND 9.000 MAXIMUM AT 400 PCT ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 101.0 ALL LOCATIONS |
UNTHREADED MOUNTING HOLE DIAMETER | 0.190 INCHES NOMINAL |