ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE ONE |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
BODY HEIGHT | 2.312 INCHES NOMINAL |
BODY LENGTH | 3.500 INCHES NOMINAL |
BODY STYLE | SINGLE POLE TYPE |
BODY WIDTH | 0.969 INCHES NOMINAL |
BOSS HEIGHT | 0.188 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
FREQUENCY IN HERTZ | 400.0 SINGLE LOCATION |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 125.0 AC SINGLE LOCATION |
MATERIAL | PLASTIC CASE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 10.0 AMPERES AC SINGLE LOCATION |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC SINGLE LOCATION |
MOUNTING FACILITY TYPE AND QUANTITY | 2 TERMINAL |
POLE QUANTITY | 1 |
RESET METHOD | MANUAL |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
TERMINAL TYPE AND QUANTITY | 1 CLIP AND 1 COMPRESSION |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 25.000 MINIMUM AT 200 PCT AND 150.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY SINGLE LOCATION |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 130.0 SINGLE LOCATION |