ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE TWO |
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | +600.0 TO 700.0 DC ALL LOCATIONS |
AUXILIARY SWITCH FUNCTION AND QUANTITY | 2 ALARM |
BODY LENGTH | 6.500 INCHES NOMINAL |
BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
BODY WIDTH | 4.125 INCHES NOMINAL |
BOSS HEIGHT | 0.187 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.562 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.375 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CRITICALITY CODE JUSTIFICATION | FEAT |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 2.750 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.625 INCHES NOMINAL |
FEATURES PROVIDED | INTERCHANGEABLE TRIP RELEASE |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MATERIAL | PLASTIC CASE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 5.0 AMPERES AC AND 5.0 AMPERES DC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 DC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.875 INCHES NOMINAL |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 DC ALL LOCATIONS |
POLE QUANTITY | 3 |
PRECIOUS MATERIAL AND LOCATION | CONTACTS SILVER |
PRECIOUS MATERIAL | SILVER |
RESET METHOD | MANUAL |
SPECIAL FEATURES | ITEM MUST COMPLY WITH REQUIREMENTS OF DESC PRODUCTION STANDARD NO. L02317; @FOR NAVY NUCLEAR PROPULSION PLANT PRODUCTS ONLY |
SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
SWITCH TERMINAL TYPE | WIRE LEAD |
TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
TRIP RELEASE AMBIENT TEMP RATING | 50.0 CELSIUS NOMINAL ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
UNTHREADED MOUNTING HOLE DIAMETER | 0.281 INCHES NOMINAL |