5925-01-048-4887 CIRCUIT BREAKER Index 5925-01-048-4889 CIRCUIT BREAKER

National Stock Number:
5925-01-048-4888

Federal Supply Class:
5925

National Item Identification Number:
010484888

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
AM12-15-220-50-474193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV


Techincal Specification:
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
ACTUATOR POSITION DESIGNATIONAT POLE ONE
RESET METHODMANUAL
TERMINAL TYPE AND QUANTITY2 THREADED STUD
MOUNTING SURFACE TO TERMINAL END DISTANCE2.461 INCHES MINIMUM AND 2.481 INCHES MAXIMUM
ARC QUENCHING METHODMAGNETIC BLOWOUT
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 SINGLE LOCATION
POLE QUANTITY1
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
BODY WIDTH0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MOUNTING FACILITY TYPE AND QUANTITY2 THREADED HOLE
FREQUENCY IN HERTZ50.0 SINGLE LOCATION
THREAD QUANTITY PER INCH32
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC SINGLE LOCATION
TRIP RELEASE METHODMAGNETIC-HYDRAULIC SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM
ACTUATOR FUNCTIONTRIP-RESET
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE15.0 AMPERES AC SINGLE LOCATION
FRAGILITY FACTORMODERATELY RUGGED
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT
CASE MATERIALPLASTIC
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT4.000 MINIMUM AT 200 PCT AND 10.000 MAXIMUM AT 200 PCT SINGLE LOCATION
BODY LENGTH2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM
NOMINAL THREAD SIZE0.138 INCHES
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
THREAD SERIES DESIGNATORUNC
BOSS HEIGHT0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM
BODY STYLESINGLE POLE TYPE
UNPACKAGED UNIT WEIGHT4.250 OUNCES NOMINAL
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS220.0 AC SINGLE LOCATION


Click here to Register for Free 30-day Trial