ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE TWO |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AUXILIARY SWITCH FUNCTION AND QUANTITY | 2 ALARM |
BODY LENGTH | 5.984 INCHES MINIMUM AND 6.016 INCHES MAXIMUM |
BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
BODY WIDTH | 4.484 INCHES MINIMUM AND 4.516 INCHES MAXIMUM |
BOSS HEIGHT | 0.202 INCHES MINIMUM AND 0.234 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.484 INCHES MINIMUM AND 1.516 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.109 INCHES MINIMUM AND 5.141 INCHES MAXIMUM |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.484 INCHES MINIMUM AND 1.516 INCHES MAXIMUM |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.577 INCHES MINIMUM AND 4.609 INCHES MAXIMUM |
FRAGILITY FACTOR | MODERATELY RUGGED |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS PROOF |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MATERIAL | PLASTIC CASE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 100.0 AMPERES AC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 15000.0 AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.983 INCHES MINIMUM AND 4.015 INCHES MAXIMUM |
NOMINAL THREAD SIZE | 0.164 INCHES |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
POLE QUANTITY | 3 |
PRECIOUS MATERIAL | SILVER |
PRECIOUS MATERIAL AND LOCATION | TERMINAL AND C0NTACT SURFACES SILVER |
RESET METHOD | MANUAL |
SPECIFICATION/STANDARD DATA | 01714-G376972-1 MANUFACTURERS SOURCE CONTROL |
SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT EACH POLE |
SWITCH TERMINAL TYPE | WIRE LEAD |
TERMINAL TYPE AND QUANTITY | 6 QUICK DISCONNECT, FEMALE |
THREAD QUANTITY PER INCH | 32 |
THREAD SERIES DESIGNATOR | UNC |
TRIP RELEASE AMBIENT TEMP RATING | 25.0 CELSIUS NOMINAL ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |