POLE QUANTITY | 4 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 72.0 AMPERES AC FIRST LOCATION |
| 72.0 AMPERES AC SECOND LOCATION |
| 72.0 AMPERES AC THIRD LOCATION |
| 100.0 MILLIAMPERES AC FOURTH LOCATION |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
TERMINAL TYPE AND QUANTITY | 8 THREADED STUD |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
RESET METHOD | MANUAL |
BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
MOUNTING FACILITY TYPE AND QUANTITY | 8 THREADED HOLE |
CASE MATERIAL | PLASTIC |
UNPACKAGED UNIT WEIGHT | 14.800 OUNCES NOMINAL |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.000 MINIMUM AT 200 PCT AND |
| 22.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
BODY LENGTH | 2.480 INCHES MINIMUM AND |
| 2.500 INCHES MAXIMUM |
BODY WIDTH | 2.990 INCHES MINIMUM AND |
| 3.010 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.925 INCHES MINIMUM AND |
| 1.955 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.715 INCHES MINIMUM AND |
| 0.745 INCHES MAXIMUM |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.050 INCHES MINIMUM AND |
| 2.070 INCHES MAXIMUM |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.715 INCHES MINIMUM AND |
| 0.745 INCHES MAXIMUM |
BOSS HEIGHT | 0.165 INCHES MAXIMUM |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.835 INCHES MAXIMUM |
THREAD SERIES DESIGNATOR | UNC |
NOMINAL THREAD SIZE | 0.138 INCHES |
THREAD QUANTITY PER INCH | 32 |
MANUAL ACTUATOR TYPE AND QUANTITY | 4 TOGGLE |
ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, THREE, AND FOUR LINKED |
AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE FOUR |
SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
SWITCH CURRENT RATING AND TYPE IN AMPS | 10.0 AC AND |
| 3.0 DC |
SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC AND |
| 50.0 DC |
SWITCH TERMINAL TYPE | QUICK DISCONNECT, MALE |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | CORROSION RESISTANT AND |
| MOISTURE RESISTANT AND |
| SHOCKPROOF AND |
| VIBRATIONPROOF AND |
| FUNGUS RESISTANT |
FEATURES PROVIDED | HIGH INRUSH PROTECTION |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
SPECIAL HANDLING FEATURE | MAGNETIC |
FRAGILITY FACTOR | MODERATELY RUGGED |