5920-01-124-9623 FUSE,CARTRIDGE Index 5945-01-124-9625 RELAY,ELECTROMAGNETIC

National Stock Number:
5925-01-124-9624

Federal Supply Class:
5925

National Item Identification Number:
011249624

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
372D522G02-374D212G011660WESTINGHOUSE ELECTRIC CORP CONTROL BUSINESS UNIT
AQBA1601-1200XT111660WESTINGHOUSE ELECTRIC CORP CONTROL BUSINESS UNIT


Techincal Specification:
POLE QUANTITY3
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE1200.0 AMPERES AC ALL LOCATIONS
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
TERMINAL TYPE AND QUANTITY6 QUICK DISCONNECT, MALE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS500.0 AC ALL LOCATIONS
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND
TIME DELAY ALL LOCATIONS
RESET METHODMANUAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
MOUNTING FACILITY TYPE AND QUANTITY4 THREADED STUD
CASE MATERIALPLASTIC
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS50000.0 AC ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING40.0 DEG CELSIUS NOMINAL ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.041 MINIMUM AT 200 PCT AND
0.045 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT140.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BODY LENGTH22.000 INCHES NOMINAL
BODY WIDTH12.000 INCHES NOMINAL
BODY HEIGHT12.243 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH14.375 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH4.000 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH13.625 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH4.000 INCHES NOMINAL
BOSS HEIGHT0.813 INCHES NOMINAL
THREAD SERIES DESIGNATORUNC
NOMINAL THREAD SIZE0.375 INCHES
THREAD QUANTITY PER INCH16
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT
FEATURES PROVIDEDADJUSTABLE TRIP RELEASE
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS2000.0 TO 6000.0 AC ALL LOCATIONS
STORAGE TYPEGENERAL PURPOSE WAREHOUSE


Click here to Register for Free 30-day Trial