ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
BODY LENGTH | 1.937 INCHES MAXIMUM |
BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
BODY WIDTH | 1.562 INCHES MAXIMUM |
BUSHING LENGTH | 0.332 INCHES MINIMUM AND 0.380 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.906 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.625 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
FREQUENCY IN HERTZ | 60.0 OR 400.0 ALL LOCATIONS |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MATERIAL | PORCELAIN CASE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 300.0 AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED BUSHING W/PANEL SEAL |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.828 INCHES MAXIMUM |
NOMINAL THREAD SIZE | 0.380 INCHES |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC ALL LOCATIONS |
POLE QUANTITY | 3 |
RESET METHOD | MANUAL |
TERMINAL TYPE AND QUANTITY | 3 WIRE HOOK |
THREAD SERIES DESIGNATOR | UNC |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 3.000 MINIMUM AT 135 PCT AND 60.000 MAXIMUM AT 135 PCT AND 0.500 MINIMUM AT 200 PCT AND 9.000 MAXIMUM AT 200 PCT AND 1.750 MAXIMUM AT 400 PCT AND 0.600 MAXIMUM AT 600 PCT AND 0.100 MAXIMUM AT 800 PCT ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 135.0 ALL LOCATIONS |
ULTIMATE TRIP TIME PER POLE IN SECONDS | 3.000 MINIMUM AND 60.000 MAXIMUM ALL LOCATIONS |