5925-01-146-9639 CIRCUIT BREAKER Index 5925-01-146-9641 CIRCUIT BREAKER

National Stock Number:
5925-01-146-9640

Federal Supply Class:
5925

National Item Identification Number:
011469640

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
203-22-2-51-502-6-3-881541SENSATA TECHNOLOGIES MARYLAND, INC


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONBETWEEN POLE ONE AND TWO
AUXILIARY SWITCH FUNCTION AND QUANTITY1 ALARM
BODY HEIGHT1.770 INCHES MAXIMUM
BODY LENGTH2.000 INCHES NOMINAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH1.540 INCHES NOMINAL
BOSS HEIGHT0.125 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.625 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE AND TWO LINKED
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE5.0 AMPERES DC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 DC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 CLIP
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS50.0 DC ALL LOCATIONS
POLE QUANTITY1
RESET METHODMANUAL
SPECIAL FEATURESHANDLE EQUIPPED WITH INTERNALLY MTD LED,24-32 VDC,RED; HANDLE COLOR BLACK; BODY COLOR GRAY
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS5.0 DC
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE ONE
SWITCH TERMINAL TYPETURRET
SWITCH VOLTAGE RATING AND TYPE IN VOLTS28.0 DC
TERMINAL TYPE AND QUANTITY4 TAB, SOLDER LUG
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.050 MINIMUM AT 200 PCT AND 0.950 MAXIMUM AT 200 PCT AND 0.020 MINIMUM AT 400 PCT AND 0.240 MAXIMUM AT 400 PCT AND 0.002 MINIMUM AT 800 PCT AND 0.060 MAXIMUM AT 800 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
ULTIMATE TRIP TIME PER POLE IN SECONDS0.200 MINIMUM AND 7.000 MAXIMUM ALL LOCATIONS


Click here to Register for Free 30-day Trial