5925-01-149-9358 CIRCUIT BREAKER Index 5925-01-149-9360 CIRCUIT BREAKER

National Stock Number:
5925-01-149-9359

Federal Supply Class:
5925

National Item Identification Number:
011499359

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
KD1-1.5A74193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
KD1-1R589946EATON CORPORATION


Techincal Specification:
ACTUATOR FUNCTIONRESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
BODY LENGTH2.150 INCHES NOMINAL
BODY STYLESINGLE POLE TYPE
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
FREQUENCY IN HERTZ50.0 OR 60.0 SINGLE LOCATION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDGENERAL PURPOSE
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 PUSH BUTTON
OVERALL DIAMETER0.635 INCHES NOMINAL
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE1.5 AMPERES AC AND 1.5 AMPERES DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC AND 200.0 DC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY1 CLIP
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC AND 32.0 DC SINGLE LOCATION
POLE QUANTITY1
RESET METHODMANUAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY2 QUICK DISCONNECT, MALE
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT4.500 MINIMUM AT 200 PCT AND 9.000 MAXIMUM AT 200 PCT SINGLE LOCATION
TRIP RELEASE AMBIENT TEMP RATING25.0 CELSIUS NOMINAL SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODTHERMAL SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT135.0 SINGLE LOCATION


Click here to Register for Free 30-day Trial