5935-01-153-7490 SOCKET,PLUG-INELECTRONICCOMPON Index 5925-01-153-7493 CIRCUIT BREAKER

National Stock Number:
5925-01-153-7491

Federal Supply Class:
5925

National Item Identification Number:
011537491

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
0N286855-198230NATIONAL SECURITY AGENCY
AM4-A8A2A2A18-A74193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
AM4-Z101-174193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
ARC QUENCHING METHODMAGNETIC BLOWOUT
AUXILIARY SWITCH FUNCTION AND QUANTITY2 ALARM
BODY LENGTH2.500 INCHES NOMINAL
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH2.060 INCHES MINIMUM AND 2.070 INCHES MAXIMUM
BOSS HEIGHT0.140 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.938 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.750 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT FIRST LOCATION
CIRCUIT PROTECTION TYPEOVERCURRENT SECOND LOCATION
CIRCUIT PROTECTION TYPEOVERCURRENT THIRD LOCATION
CIRCUIT PROTECTION TYPEUNDERVOLTAGE FOURTH LOCATION
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.062 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.750 INCHES NOMINAL
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, THREE, AND FOUR LINKED
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ50.0 OR 60.0 FIRST LOCATION
FREQUENCY IN HERTZ50.0 OR 60.0 SECOND LOCATION
FREQUENCY IN HERTZ50.0 OR 60.0 THIRD LOCATION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT
INTERNAL TRIP RELEASE CONFIGURATIONRELAY TRIP FOURTH LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP FIRST LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SECOND LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP THIRD LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY4 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE30.0 AMPERES AC FIRST LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE30.0 AMPERES AC SECOND LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE30.0 AMPERES AC THIRD LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS2000.0 DC FOURTH LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC FIRST LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC SECOND LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC THIRD LOCATION
MOUNTING FACILITY TYPE AND QUANTITY8 THREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE2.409 INCHES MINIMUM AND 2.533 INCHES MAXIMUM
NOMINAL THREAD SIZE0.138 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS102.0 DC FOURTH LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC SECOND LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC THIRD LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC FIRST LOCATION
POLE QUANTITY4
RESET METHODMANUAL
SPECIAL HANDLING FEATUREMAGNETIC
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SWITCH CONTACT ARRANGEMENTDOUBLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS10.0 AC AND 4.0 DC
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE TWO AND INTERNAL AT POLE THREE
SWITCH TERMINAL TYPETAB, SOLDER LUG
SWITCH VOLTAGE RATING AND TYPE IN VOLTS250.0 AC AND 30.0 DC
TERMINAL TYPE AND QUANTITY8 THREADED STUD
THREAD QUANTITY PER INCH32
THREAD SERIES DESIGNATORUNC
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT3.000 MINIMUM AT 200 PCT AND 11.000 MAXIMUM AT 200 PCT FIRST LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT3.000 MINIMUM AT 200 PCT AND 11.000 MAXIMUM AT 200 PCT SECOND LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT3.000 MINIMUM AT 200 PCT AND 11.000 MAXIMUM AT 200 PCT THIRD LOCATION
TRIP RELEASE CHARACTERISTICINSTANTANEOUS FOURTH LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY FIRST LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SECOND LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY THIRD LOCATION
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
UNPACKAGED UNIT WEIGHT12.500 OUNCES NOMINAL


Click here to Register for Free 30-day Trial