5925

National Item Identification Number:
011702272

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
2101-300533783BR COMMUNICATIONS INC
AP114-7480-181541SENSATA TECHNOLOGIES MARYLAND, INC


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONBETWEEN POLE ONE AND TWO
BODY LENGTH1.562 INCHES MAXIMUM
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH1.281 INCHES MAXIMUM
BUSHING LENGTH0.380 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH0.875 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.625 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 OR 400.0 FIRST LOCATION
FREQUENCY IN HERTZ60.0 OR 400.0 SECOND LOCATION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDHERMETICALLY SEALED AND SHOCKPROOF AND VIBRATIONPROOF
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE500.0 MILLIAMPERES AC SECOND LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE500.0 MILLIAMPERES AC FIRST LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 DC THIRD LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC FIRST LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC SECOND LOCATION
MOUNTING FACILITY TYPE AND QUANTITY1 THREADED BUSHING W/PANEL SEAL
MOUNTING SURFACE TO TERMINAL END DISTANCE1.780 INCHES MAXIMUM
NOMINAL THREAD SIZE0.375 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS12.0 DC THIRD LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC FIRST LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC SECOND LOCATION
POLE QUANTITY3
RESET METHODMANUAL
SPECIAL FEATURESPOLE THREE IS A SWITCH
SPECIAL HANDLING FEATUREMAGNETIC
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY4 WIRE HOOK
THREAD SERIES DESIGNATORUNEF
THREAD QUANTITY PER INCH32
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.055 MINIMUM AT 200 PCT AND 0.950 MAXIMUM AT 200 PCT FIRST LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.055 MINIMUM AT 200 PCT AND 0.950 MAXIMUM AT 200 PCT SECOND LOCATION
TRIP RELEASE CHARACTERISTICINSTANTANEOUS THIRD LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY FIRST LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SECOND LOCATION
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
UNPACKAGED UNIT WEIGHT3.600 OUNCES NOMINAL