5925-01-180-0079 CIRCUIT BREAKER Index 5925-01-180-0081 CIRCUIT BREAKER

National Stock Number:
5925-01-180-0080

Federal Supply Class:
5925

National Item Identification Number:
011800080

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
985611-00216224TITAN CORP THE
985611-00263702L-3 SERVICES, INC. DBA COMMAND & CONTROL SYSTEMS SOFTWARE & EXPEDITIONARY OPERATION
APG-6668-1REC3-8420-281541SENSATA TECHNOLOGIES MARYLAND, INC


Techincal Specification:
POLE QUANTITY4
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE5.0 AMPERES AC FIRST LOCATION
5.0 AMPERES AC SECOND LOCATION
5.0 AMPERES AC THIRD LOCATION
30.0 AMPERES DC FOURTH LOCATION
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
TERMINAL TYPE AND QUANTITY10 TAB W/SCREW
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC FIRST LOCATION
250.0 AC SECOND LOCATION
250.0 AC THIRD LOCATION
65.0 DC FOURTH LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY FIRST LOCATION
TIME DELAY SECOND LOCATION
TIME DELAY THIRD LOCATION
INSTANTANEOUS FOURTH LOCATION
RESET METHODMANUAL
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
MOUNTING FACILITY TYPE AND QUANTITY8 THREADED HOLE
CASE MATERIALPLASTIC
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
FREQUENCY IN HERTZ50.0 OR
60.0 FIRST LOCATION
50.0 OR
60.0 SECOND LOCATION
60.0 THIRD LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC FIRST LOCATION
1000.0 AC SECOND LOCATION
1000.0 AC THIRD LOCATION
2000.0 DC FOURTH LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP FIRST LOCATION
SERIES TRIP SECOND LOCATION
SERIES TRIP THIRD LOCATION
RELAY TRIP FOURTH LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.130 MINIMUM AT 200 PCT AND
1.300 MAXIMUM AT 200 PCT FIRST LOCATION
1.300 MAXIMUM AT 200 PCT SECOND LOCATION
0.130 MINIMUM AT 200 PCT AND
1.300 MAXIMUM AT 200 PCT THIRD LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 FIRST LOCATION
125.0 SECOND LOCATION
125.0 THIRD LOCATION
150.0 FOURTH LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BUSHING LENGTH0.130 INCHES NOMINAL
BODY LENGTH2.000 INCHES NOMINAL
BODY WIDTH3.015 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.530 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.750 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH1.660 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.750 INCHES NOMINAL
MOUNTING SURFACE TO TERMINAL END DISTANCE2.032 INCHES MAXIMUM
THREAD SERIES DESIGNATORUNC
NOMINAL THREAD SIZE0.138 INCHES
THREAD QUANTITY PER INCH32
MANUAL ACTUATOR TYPE AND QUANTITY2 TOGGLE
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO AND
AT POLE THREE
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTTWO AND THREE LINKED
AUXILIARY SWITCH FUNCTION AND QUANTITY1 ALARM
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE ONE
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS10.0 AC AND
3.0 DC
SWITCH VOLTAGE RATING AND TYPE IN VOLTS250.0 AC AND
50.0 DC
SWITCH TERMINAL TYPETAB, SOLDER LUG
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT
STORAGE TYPEGENERAL PURPOSE WAREHOUSE


Click here to Register for Free 30-day Trial