5925-01-188-4300 CIRCUIT BREAKER Index 5925-01-188-4302 CIRCUIT BREAKER

National Stock Number:
5925-01-188-4301

Federal Supply Class:
5925

National Item Identification Number:
011884301

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
10M10-26276301THE BOEING COMPANY
AM4-A3A3A3A18-A-30-274193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
AM4-A3A3A3A18-A-30-2 P4-107VRDC74193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
AM4-Z1 48-174193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
UPL9111-23722-281541SENSATA TECHNOLOGIES MARYLAND, INC
IULHK9111-23722-282647SENSATA TECHNOLOGIES, INC.


Techincal Specification:
POLE QUANTITY4
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE30.0 AMPERES AC ALL LOCATIONS
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
TERMINAL TYPE AND QUANTITY10 THREADED STUD
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
RESET METHODMANUAL
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
MOUNTING FACILITY TYPE AND QUANTITY8 THREADED HOLE
CASE MATERIALPLASTIC
UNPACKAGED UNIT WEIGHT12.500 OUNCES NOMINAL
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONS
FREQUENCY IN HERTZ50.0 OR
60.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP FIRST LOCATION
SERIES TRIP SECOND LOCATION
SERIES TRIP THIRD LOCATION
RELAY TRIP FOURTH LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT2.000 MINIMUM AT 200 PCT AND
20.000 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BODY LENGTH2.490 INCHES MINIMUM AND
2.510 INCHES MAXIMUM
BODY WIDTH2.990 INCHES MINIMUM AND
3.010 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.928 INCHES MINIMUM AND
1.948 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.740 INCHES MINIMUM AND
0.760 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.052 INCHES MINIMUM AND
2.062 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.740 INCHES MINIMUM AND
0.760 INCHES MAXIMUM
BOSS HEIGHT0.130 INCHES MINIMUM AND
0.150 INCHES MAXIMUM
MOUNTING SURFACE TO TERMINAL END DISTANCE2.461 INCHES MINIMUM AND
2.481 INCHES MAXIMUM
THREAD SERIES DESIGNATORUNC
NOMINAL THREAD SIZE0.138 INCHES
THREAD QUANTITY PER INCH32
MANUAL ACTUATOR TYPE AND QUANTITY4 TOGGLE
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, THREE, AND FOUR LINKED
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND
MOISTURE RESISTANT
ARC QUENCHING METHODMAGNETIC BLOWOUT
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SPECIAL HANDLING FEATUREMAGNETIC
FRAGILITY FACTORMODERATELY RUGGED


Click here to Register for Free 30-day Trial