ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE TWO |
BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
OVERALL HEIGHT | 4.750 INCHES NOMINAL |
OVERALL LENGTH | 15.500 INCHES NOMINAL |
OVERALL WIDTH | 9.000 INCHES NOMINAL |
MATERIAL | PLASTIC CASE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 1400.0 AMPERES AC AND 1400.0 AMPERES DC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 42000.0 AC AND 20000.0 DC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC AND 250.0 DC ALL LOCATIONS |
POLE QUANTITY | 3 |
RESET METHOD | MANUAL |
TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
TRIP RELEASE AMBIENT TEMP RATING | 77.0 FAHRENHEIT NOMINAL ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 4000.000 MINIMUM AT 200 PCT AND 8000.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
UNTHREADED MOUNTING HOLE DIAMETER | 0.500 INCHES NOMINAL |