5920-01-195-2300 FUSE LINK,THERMAL Index 5925-01-195-2302 CIRCUIT BREAKER

National Stock Number:
5925-01-195-2301

Federal Supply Class:
5925

National Item Identification Number:
011952301

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
JE1-W3-A-15-274193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
JE1S-W3-0015-02EL3330HEINEMANN ELECTRIC CANADA LIMITEE
JEIS-W3-0015-02E1W134EATON CORP AEROSPACE COMMERCIAL CONTROLS DIV
JE1S-W3-A-0015-02E74193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
JE1S-W3-A-15-274193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
BODY LENGTH2.000 INCHES NOMINAL
BODY STYLESINGLE POLE TYPE
BODY WIDTH0.750 INCHES NOMINAL
BUSHING LENGTH0.375 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.560 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
FREQUENCY IN HERTZ400.0 SINGLE LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE15.0 AMPERES AC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY1 THREADED BUSHING
MOUNTING SURFACE TO TERMINAL END DISTANCE1.941 INCHES NOMINAL
NOMINAL THREAD SIZE0.375 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC SINGLE LOCATION
POLE QUANTITY1
RESET METHODMANUAL
TERMINAL TYPE AND QUANTITY2 QUICK DISCONNECT, MALE
THREAD SERIES DESIGNATORUNEF
THREAD QUANTITY PER INCH32
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODMAGNETIC-HYDRAULIC SINGLE LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT2.200 MINIMUM AT 200 PCT AND 22.000 MAXIMUM AT 200 PCT SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 SINGLE LOCATION


Click here to Register for Free 30-day Trial