5985-01-224-3543 COUPLING,WAVEGUIDE Index 5950-01-224-3545 TRANSFORMER ASSEMBLY

National Stock Number:
5925-01-224-3544

Federal Supply Class:
5925

National Item Identification Number:
012243544

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
34B2108102WESTFALL EQUIPMENT CO
6963515434CUMMINS INC.
79Z1508D127315MORRIS MATERIAL HANDLING, INC.


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
BODY LENGTH1.266 INCHES NOMINAL
BODY STYLESINGLE POLE TYPE
BODY WIDTH3.000 INCHES NOMINAL
BUSHING LENGTH0.422 INCHES NOMINAL
CASE MATERIALPLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.574 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 SINGLE LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 PUSH BUTTON
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE60.0 AMPERES AC SINGLE LOCATION AND 60.0 AMPERES DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS900.0 AC SINGLE LOCATION AND 900.0 DC SINGLE LOCATION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDWEATHERPROOF
POLE QUANTITY1
PROPRIETARY CHARACTERISTICSPACS
MOUNTING FACILITY TYPE AND QUANTITY2 UNTHREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE0.687 INCHES NOMINAL
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS110.0 AC SINGLE LOCATION AND 30.0 DC SINGLE LOCATION
RESET METHODMANUAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY2 SCREW
TRIP RELEASE AMBIENT TEMP RATING77.0 DEG FAHRENHEIT NOMINAL SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODTHERMAL SINGLE LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT6.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 50.000 MAXIMUM AT 200 PCT SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT130.0 SINGLE LOCATION
UNPACKAGED UNIT WEIGHT0.312 POUNDS
UNTHREADED MOUNTING HOLE DIAMETER0.250 INCHES NOMINAL