5925-01-225-9332 CIRCUIT BREAKER Index 5985-01-225-9334 SWITCH,RADIO FREQUENCY TRANSMISS

National Stock Number:
5925-01-225-9333

Federal Supply Class:
5925

National Item Identification Number:
012259333

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
56-002-00289022TDK-LAMBDA AMERICAS INC.
JA3-Z-301-274193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
UPGH667-2995-181541SENSATA TECHNOLOGIES MARYLAND, INC


Techincal Specification:
POLE QUANTITY3
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE25.0 AMPERES AC FIRST LOCATION
25.0 AMPERES AC SECOND LOCATION
5.0 AMPERES AC THIRD LOCATION
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
TERMINAL TYPE AND QUANTITY6 SCREW
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY FIRST LOCATION
TIME DELAY SECOND LOCATION
INSTANTANEOUS THIRD LOCATION
RESET METHODMANUAL
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
MOUNTING FACILITY TYPE AND QUANTITY6 THREADED HOLE
CASE MATERIALPLASTIC
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
FREQUENCY IN HERTZ50.0 OR
60.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP FIRST LOCATION
SERIES TRIP SECOND LOCATION
RELAY TRIP THIRD LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT2.200 MINIMUM AT 200 PCT AND
20.000 MAXIMUM AT 200 PCT FIRST LOCATION
2.200 MINIMUM AT 200 PCT AND
20.000 MAXIMUM AT 200 PCT SECOND LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BUSHING LENGTH0.130 INCHES NOMINAL
BODY LENGTH2.000 INCHES NOMINAL
BODY WIDTH2.250 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.531 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.750 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH1.656 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.750 INCHES NOMINAL
MOUNTING SURFACE TO TERMINAL END DISTANCE1.898 INCHES NOMINAL
THREAD SERIES DESIGNATORUNC
NOMINAL THREAD SIZE0.138 INCHES
THREAD QUANTITY PER INCH32
MANUAL ACTUATOR TYPE AND QUANTITY3 TOGGLE
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDGENERAL PURPOSE
FEATURES PROVIDEDHIGH INRUSH PROTECTION
ARC QUENCHING METHODMAGNETIC BLOWOUT
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SPECIAL HANDLING FEATUREMAGNETIC
FRAGILITY FACTORMODERATELY RUGGED
SPECIAL FEATURESRELAY COIL HAS A SPECIAL ELECTRICAL SHORT FOR MECHANICAL TRIP