AUXILIARY TRIP COIL VOLTAGE TYPE AND RATING IN VOLTS | 115.0 AC NOMINAL ALL LOCATIONS |
BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP W/AUXILIARY LOAD TERMINAL AND REMOTE TRIP FEATURE ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OVERALL HEIGHT | 4.250 INCHES NOMINAL |
OVERALL LENGTH | 3.688 INCHES NOMINAL |
OVERALL WIDTH | 3.250 INCHES NOMINAL |
MATERIAL | PLASTIC CASE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 40.0 AMPERES AC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 216.0 AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 115.0 AC ALL LOCATIONS |
POLE QUANTITY | 3 |
RESET ACTUATOR VOLTAGE RATING AND TYPE IN VOLTS | 115.0 AC |
RESET METHOD | ELECTRIC |
TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
TRIP RELEASE DUTY CYCLE | CONTINUOUS ALL LOCATIONS |
TRIP RELEASE METHOD | THERMAL ALL LOCATIONS |
TRIP RELEASE AMBIENT TEMP RATING | -54.0 CELSIUS MINIMUM AND 71.0 CELSIUS MAXIMUM ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 138.0 ALL LOCATIONS |
ULTIMATE TRIP TIME PER POLE IN SECONDS | 60.000 MAXIMUM ALL LOCATIONS |
UNTHREADED MOUNTING HOLE DIAMETER | 0.172 INCHES NOMINAL |