5925-01-226-8319 CIRCUIT BREAKER Index 5330-01-226-8321 PACKING,PREFORMED

National Stock Number:
5925-01-226-8320

Federal Supply Class:
5925

National Item Identification Number:
012268320

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
0015955-0010C9D4PERATON INC
AM3-Z343-174193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
AM3RA15A2A3LC07DA252/115ACP0NUY1WES-GARDE COMPONENTS GROUP, INC.
AM3RA15A2ALC07DA252/115ACP0NUY1WES-GARDE COMPONENTS GROUP, INC.
AM3R-A15A2A3-LC-07-D-A-25-2-V11-4AGL7EATON CORPORATION
NAM3S-Z68-181118EATON CORPORATION
NAM3S-Z82-181118EATON CORPORATION


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
ARC QUENCHING METHODMAGNETIC BLOWOUT
AUXILIARY SWITCH FUNCTION AND QUANTITY1 ALARM
AUXILIARY TRIP COIL VOLTAGE TYPE AND RATING IN VOLTS115.0 AC NOMINAL FIRST LOCATION
BODY LENGTH2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH2.240 INCHES MINIMUM AND 2.251 INCHES MAXIMUM
BOSS HEIGHT0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SECOND LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP THIRD LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP W/REMOTE TRIP FEATURE FIRST LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY3 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE25.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY6 THREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE2.461 INCHES MINIMUM AND 2.481 INCHES MAXIMUM
NOMINAL THREAD SIZE0.138 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC ALL LOCATIONS
POLE QUANTITY3
RESET METHODMANUAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SUPPLEMENTARY FEATURESEXTRA LONG PART NUMBER 4AGL7/AM3R-A15A2A3-LC-07-D-A-25-2-V115P
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS0.1 AC AND 0.1 DC
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE TWO
SWITCH TERMINAL TYPEQUICK DISCONNECT, MALE
SWITCH VOLTAGE RATING AND TYPE IN VOLTS125.0 AC AND 30.0 DC
TERMINAL TYPE AND QUANTITY7 THREADED STUD
THREAD SERIES DESIGNATORUNC
THREAD QUANTITY PER INCH32
TRIP RELEASE CHARACTERISTICTIME DELAY SECOND LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY THIRD LOCATION
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND TIME DELAY FIRST LOCATION
TRIP RELEASE DUTY CYCLEINTERMITTENT FIRST LOCATION
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT4.000 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT SECOND LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT4.000 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT THIRD LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS