ACTUATOR FUNCTION | RESET |
ACTUATOR POSITION DESIGNATION | AT POLE ONE |
ARC QUENCHING METHOD | AIR |
BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
FRAGILITY FACTOR | MODERATELY RUGGED |
FREQUENCY IN HERTZ | 50.0 OR 60.0 SINGLE LOCATION |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 PUSH BUTTON |
OVERALL HEIGHT | 0.760 INCHES MAXIMUM |
OVERALL LENGTH | 1.535 INCHES MAXIMUM |
OVERALL WIDTH | 0.760 INCHES MAXIMUM |
MATERIAL | PLASTIC CASE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 5.0 AMPERES AC AND 5.0 AMPERES DC SINGLE LOCATION |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC AND 1000.0 DC SINGLE LOCATION |
MOUNTING FACILITY TYPE AND QUANTITY | 2 CLIP |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC AND 32.0 DC SINGLE LOCATION |
POLE QUANTITY | 1 |
RESET METHOD | MANUAL |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
TERMINAL TYPE AND QUANTITY | 2 QUICK DISCONNECT, MALE |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.200 MINIMUM AT 200 PCT AND 15.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
TRIP RELEASE AMBIENT TEMP RATING | 25.0 CELSIUS NOMINAL SINGLE LOCATION |
TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
TRIP RELEASE METHOD | THERMAL SINGLE LOCATION |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 135.0 SINGLE LOCATION |
UNPACKAGED UNIT WEIGHT | 0.350 OUNCES NOMINAL |