ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE ONE |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
FRAGILITY FACTOR | MODERATELY RUGGED |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
OVERALL HEIGHT | 2.000 INCHES NOMINAL |
OVERALL LENGTH | 7.125 INCHES NOMINAL |
OVERALL WIDTH | 3.000 INCHES NOMINAL |
MATERIAL | PLASTIC CASE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 175.0 AMPERES DC SINGLE LOCATION |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 14000.0 DC SINGLE LOCATION |
MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
NOMINAL THREAD SIZE | 0.190 INCHES |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 160.0 DC SINGLE LOCATION |
POLE QUANTITY | 1 |
RESET METHOD | MANUAL |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
TERMINAL TYPE AND QUANTITY | 2 COMPRESSION |
THREAD SERIES DESIGNATOR | UNF |
THREAD QUANTITY PER INCH | 32 |
TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
TRIP RELEASE METHOD | MAGNETIC SINGLE LOCATION |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 25.000 MINIMUM AT 200 PCT AND 200.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |