5925-01-294-4584 CIRCUIT BREAKER Index 5930-01-294-4586 SWITCH,HOOK

National Stock Number:
5925-01-294-4585

Federal Supply Class:
5925

National Item Identification Number:
012944585

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
JJ63M35030086L3HARRIS MARITIME POWER & ENERGY SOLUTIONS, INC.
JXD63M35066842SIEMENS ENERGY AND AUTOMATION INC ITE CIRCUIT PROTECTION DIV


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS+2000.0 TO 4000.0 AC AND +2000.0 TO 4000.0 DC ALL LOCATIONS
ARC QUENCHING METHODMAGNETIC BLOWOUT
BODY STYLERECTANGULAR DIMENSIONAL ENVELOPE
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FEATURES PROVIDEDADJUSTABLE TRIP RELEASE
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
OVERALL HEIGHT4.000 INCHES NOMINAL
OVERALL LENGTH11.000 INCHES NOMINAL
OVERALL WIDTH7.500 INCHES NOMINAL
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE350.0 AMPERES AC AND 350.0 AMPERES DC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS22000.0 AC AND 18000.0 DC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 UNTHREADED HOLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS600.0 AC AND 250.0 DC ALL LOCATIONS
POLE QUANTITY3
RESET METHODMANUAL
SPECIAL HANDLING FEATUREMAGNETIC
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY6 COMPRESSION
TRIP RELEASE AMBIENT TEMP RATING50.0 CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTICINSTANTANEOUS ALL LOCATIONS
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
UNTHREADED MOUNTING HOLE DIAMETER0.250 INCHES NOMINAL