5925-01-304-0361 CIRCUIT BREAKER Index 5925-01-304-0363 CIRCUIT BREAKER

National Stock Number:
5925-01-304-0362

Federal Supply Class:
5925

National Item Identification Number:
013040362

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
UPGN-666-1-42-752M81541SENSATA TECHNOLOGIES MARYLAND, INC


Techincal Specification:
AUXILIARY SWITCH FUNCTION AND QUANTITY1 CONTROL
BODY LENGTH2.000 INCHES NOMINAL
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH0.750 INCHES NOMINAL
BUSHING LENGTH0.625 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.530 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FREQUENCY IN HERTZ400.0 ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE7.5 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS2100.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY6 THREADED STUD
MOUNTING SURFACE TO TERMINAL END DISTANCE2.232 INCHES MAXIMUM
NOMINAL THREAD SIZE0.187 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC ALL LOCATIONS
POLE QUANTITY3
RESET METHODMANUAL
TERMINAL TYPE AND QUANTITY6 SCREW
THREAD SERIES DESIGNATORUNC
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT5.000 MINIMUM AT 150 PCT AND 70.000 MAXIMUM AT 150 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0 ALL LOCATIONS
ULTIMATE TRIP TIME PER POLE IN SECONDS70.000 MAXIMUM ALL LOCATIONS