POLE QUANTITY | 2 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 7.0 AMPERES AC FIRST LOCATION |
| 3.5 AMPERES AC SECOND LOCATION |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
TERMINAL TYPE AND QUANTITY | 4 TAB, SOLDER LUG |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
RESET METHOD | MANUAL |
BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
MOUNTING FACILITY TYPE AND QUANTITY | 2 CLIP |
CASE MATERIAL | PLASTIC |
TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.300 MINIMUM AT 135 PCT AND |
| 7.000 MAXIMUM AT 135 PCT ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OVERALL LENGTH | 1.823 INCHES NOMINAL |
OVERALL HEIGHT | 0.400 INCHES NOMINAL |
OVERALL WIDTH | 1.560 INCHES NOMINAL |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | BETWEEN POLE ONE AND TWO |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND |
| GENERAL PURPOSE |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
FRAGILITY FACTOR | MODERATELY RUGGED |