5925-01-313-0959 CIRCUIT BREAKER Index 5999-01-313-0961 SHIELDING GASKET,ELECTRONIC

National Stock Number:
5925-01-313-0960

Federal Supply Class:
5925

National Item Identification Number:
013130960

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
MIL-C-580981349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
MS25361-50V0U583SAE INTERNATIONAL
SAE-AS580910U583SAE INTERNATIONAL
MS25361-50V96906MILITARY STANDARDS PROMULGATED BY MILITARY DEPARTMENTS UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M


Techincal Specification:
POLE QUANTITY1
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE50.0 AMPERES AC AND
50.0 AMPERES DC SINGLE LOCATION
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
TERMINAL TYPE AND QUANTITY2 TAB W/SCREW
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS200.0 AC AND
28.0 DC SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
RESET METHODMANUAL
BODY STYLESINGLE POLE TYPE
MOUNTING FACILITY TYPE AND QUANTITY2 THREADED HOLE
TRIP RELEASE METHODTHERMAL SINGLE LOCATION
FREQUENCY IN HERTZ60.0 SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS3500.0 AC AND
6000.0 DC SINGLE LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
TRIP RELEASE AMBIENT TEMP RATING40.0 DEG CELSIUS NOMINAL SINGLE LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT15.000 MINIMUM AT 200 PCT AND
65.000 MAXIMUM AT 200 PCT SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0 SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BUSHING LENGTH0.454 INCHES MINIMUM AND
0.516 INCHES MAXIMUM
BODY LENGTH2.189 INCHES MAXIMUM
BODY WIDTH0.750 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.439 INCHES MINIMUM AND
1.501 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH1.807 INCHES MINIMUM AND
1.817 INCHES MAXIMUM
MOUNTING SURFACE TO TERMINAL END DISTANCE2.250 INCHES MAXIMUM
THREAD SERIES DESIGNATORUNC
NOMINAL THREAD SIZE0.138 INCHES
THREAD QUANTITY PER INCH32
MANUAL ACTUATOR TYPE AND QUANTITY1 PUSH-PULL
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDVIBRATIONPROOF
TEST DATA DOCUMENT81349-MIL-C-5809 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.).
ARC QUENCHING METHODMAGNETIC BLOWOUT
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
FRAGILITY FACTORMODERATELY RUGGED
SPECIFICATION/STANDARD DATA96906-MS25361 GOVERNMENT STANDARD


Click here to Register for Free 30-day Trial