Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
CF3-G2G3G3-U-15-240-174193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
AUXILIARY SWITCH FUNCTION AND QUANTITY1 ALARM
BODY HEIGHT2.827 INCHES NOMINAL
BODY LENGTH5.844 INCHES NOMINAL
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH3.103 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH1.026 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH4.750 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH5.032 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH1.026 INCHES NOMINAL
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
FREQUENCY IN HERTZ50.0 OR 60.0 ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY3 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE15.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS5000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY3 SLOT AND 3 THREADED HOLE
MOUNTING SLOT WIDTH0.164 INCHES NOMINAL
NOMINAL THREAD SIZE0.138 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC ALL LOCATIONS
POLE QUANTITY3
RESET METHODMANUAL
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS10.0 AC AND 5.0 DC
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE ONE
SWITCH TERMINAL TYPETAB, SOLDER LUG
SWITCH VOLTAGE RATING AND TYPE IN VOLTS250.0 AC AND 50.0 DC
TERMINAL TYPE AND QUANTITY2 THREADED STUD
THREAD QUANTITY PER INCH32
THREAD SERIES DESIGNATORUNC
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT5.000 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS