ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
BODY LENGTH | 5.125 INCHES NOMINAL |
BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
BODY WIDTH | 3.108 INCHES NOMINAL |
BOSS HEIGHT | 0.220 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.996 INCHES MINIMUM AND 1.056 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.480 INCHES MINIMUM AND 3.614 INCHES MAXIMUM |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.750 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.026 INCHES NOMINAL |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT AND SALT WATER RESISTANT |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
MATERIAL | PLASTIC CASE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 70.0 AMPERES AC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 700.0 AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.460 INCHES MINIMUM AND 3.580 INCHES MAXIMUM |
NOMINAL THREAD SIZE | 0.138 INCHES |
POLE QUANTITY | 3 |
RESET METHOD | MANUAL |
SPECIAL FEATURES | CIRCUIT BREAKER HAS THREE POLE, SINGLE THROW NORMALLY OPEN SWITCH CONTACT ARRANGEMENT; MOUNT IN VERTICAL PLANE |
SPECIFICATION/STANDARD DATA | 81349-MIL-C-55629/17 GOVERNMENT SPECIFICATION |
SWITCH CURRENT RATING AND TYPE IN AMPS | 5.0 AC AND 1.0 DC |
SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE |
SWITCH TERMINAL TYPE | PIN |
SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC AND 50.0 DC |
TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
TEST DATA DOCUMENT | 81349-MIL-C-55629 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). |
THREAD QUANTITY PER INCH | 32 |
THREAD SERIES DESIGNATOR | UNC |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.150 MINIMUM AT 200 PCT AND 1.000 MAXIMUM AT 200 PCT AND 0.032 MINIMUM AT 400 PCT AND 0.250 MAXIMUM AT 400 PCT AND 0.110 MAXIMUM AT 800 PCT ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 1000.0 ALL LOCATIONS |
ULTIMATE TRIP TIME PER POLE IN SECONDS | 0.800 MINIMUM AND 7.000 MAXIMUM ALL LOCATIONS |