ACTUATOR FUNCTION | TRIP W/SEPARATE RESET |
ACTUATOR POSITION DESIGNATION | AT POLE TWO |
BODY HEIGHT | 3.440 INCHES NOMINAL |
BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
BODY WIDTH | 5.340 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
FREQUENCY IN HERTZ | 50.0 OR 60.0 ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MATERIAL | PLASTIC CASE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 200.0 AMPERES AC AND 200.0 AMPERES DC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 65000.0 AC AND 10000.0 DC ALL LOCATIONS |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC AND 250.0 DC ALL LOCATIONS |
POLE QUANTITY | 4 |
RESET METHOD | MANUAL |
SPECIAL FEATURES | DC RATINGS ARE OF 2-POLES OF 3-POLE CIRCUIT; TRIP UNIT - THERMAL AND MAGNETIC ARE ADJUSTABLE; RATED ULTIMATE BREAKING CAPACITIES - 65000.0 AMPS AT 220.0 TO 240.0 VOLTS AC; 25000.0 AMPS AT 380.0 TO 415.0 VOLTS AC; 25000.0 AMPS AT 480.0 VOLTS AC; 18000.0 AMPS AT 600.0 VOLTS AC; 12000.0 AMPS AT 690.0 VOLTS AC; 10000.0 AMPS AT 250.0 VOLTS DC; OVERALL HEIGHT 7.000 INCHES NOMINAL; INCLUDES FREEZE TESTED OPTION (F02) USING SPECIAL LUBRICATION, MECHANICAL OPERATION IS VERIFIED TO MINUS 40.0 DEGREES C; ALSO INCLUDES STANDARD SHUNT TRIP OPTION (SNT120CPK) 120.0 VOLTS AC. 50.0 TO 60.0 HERTZ, 110.0 TO 125.0 VOLTS DC. MOUNTED IN RIGHT-HAND CAVITY LEFT POLE POSITION |
TRIP RELEASE AMBIENT TEMP RATING | 40.0 CELSIUS NOMINAL ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |