5950-00-814-1784 TRANSFORMER,RADIO FREQUENCY Index 5970-00-814-1788 INSULATING COMPOUND KIT,ELECTRIC

National Stock Number:
5945-00-814-1787

Federal Supply Class:
5945

National Item Identification Number:
008141787

Description:
RELAY,ELECTROMAGNETIC

Detail:
A relay which is actuated by the effect of a magnetic field developed by the current in its energizing coil(s). Includes solenoid and armature types. Excludes CONTACTOR, MAGNETIC; RELAY, METER MOVEMENT; RELAY, MOTOR DRIVEN; RELAY, REED; RELAY, RESONANT REED; RELAY, ROTARY; and SWITCH, STEPPING.


Manufacturer Information:
2913290KDP7KIDDE-FENWAL, LLC
29132916004DAVEY COMPRESSOR CO DIV OF KECO INDUSTRIES INC
6042H16015605EATON CORP OPNS & TECHNICAL CENTER
6042H16027192DRS NAVAL POWER SYSTEMS INC
MIL-PRF-610681349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
6042H16081640SAFRAN POWER USA, LLC
MIL-R-610681349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
MS24141-D296906MILITARY STANDARDS PROMULGATED BY MILITARY DEPARTMENTS UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M


Techincal Specification:
DUTY TYPECONTINUOUS
ARC QUENCHING METHODAIR
AUXILIARY CONTACT LOAD CURRENT RATING AT MAXIMUM RATED VOLTAGE5.0 AMPERES AC AND 5.0 AMPERES DC INDUCTIVE LOAD
AUXILIARY CONTACT LOAD CURRENT RATING AT MAXIMUM RATED VOLTAGE5.0 AMPERES AC AND 5.0 AMPERES DC RESISTIVE LOAD
AUXILIARY CONTACT LOAD CURRENT RATING AT MAXIMUM RATED VOLTAGE750.0 MILLIAMPERES AC AND 750.0 MILLIAMPERES DC LAMP LOAD
AUXILIARY CONTACT MAXIMUM VOLTAGE RATING IN VOLTS115.0 AC AND 28.0 DC
CENTER TO CENTER DISTANCE BETWEEN MOUNTING FACILITIES PARALLEL TO LENGTH2.990 INCHES MINIMUM AND 3.010 INCHES MAXIMUM SINGLE MOUNTING FACILITY
COIL QUANTITY1
CUBIC MEASURE55.445 CUBIC INCHES
ENVIRONMENTAL PROTECTIONHERMETIC
FRAGILITY FACTORMODERATELY RUGGED
MAIN CONTACT LOAD CURRENT RATING AT MAXIMUM RATED VOLTAGE100.0 AMPERES DC INDUCTIVE LOAD
MAIN CONTACT LOAD CURRENT RATING AT MAXIMUM RATED VOLTAGE100.0 AMPERES AC AND 100.0 AMPERES DC RESISTIVE LOAD
MAIN CONTACT LOAD CURRENT RATING AT MAXIMUM RATED VOLTAGE50.0 AMPERES AC AND 50.0 AMPERES DC LAMP LOAD
MAIN CONTACT LOAD CURRENT RATING AT MAXIMUM RATED VOLTAGE75.0 AMPERES AC AND 100.0 AMPERES DC MOTOR LOAD
MAIN CONTACT MAXIMUM VOLTAGE RATING IN VOLTS115.0 AC AND 28.0 DC
OVERALL HEIGHT4.595 INCHES MAXIMUM
OVERALL LENGTH3.640 INCHES MAXIMUM
OVERALL WIDTH3.315 INCHES MAXIMUM
MOUNTING FACILITY TYPE AND QUANTITY2 UNTHREADED HOLE SINGLE MOUNTING FACILITY
MOUNTING FACILITY PATTERNIN-LINE SINGLE MOUNTING FACILITY
NOMINAL OPERATING CURRENT RATING AND TYPE500.0 MILLIAMPERES DC SINGLE WINDING
NONPILE-UP AUXILIARY CONTACT ARRANGEMENT1 POLE, SINGLE THROW, NORMALLY CLOSED, DOUBLE BREAK, MOMENTARY ACTION AND 1 POLE, SINGLE THROW, NORMALLY OPEN, DOUBLE MAKE, MOMENTARY ACTION
NONPILE-UP MAIN CONTACT ARRANGEMENT1 POLE, SINGLE THROW, NORMALLY OPEN, DOUBLE MAKE, MOMENTARY ACTION
OPERATING VOLTAGE RATING AND TYPE AT SPECIFIED TEMP28.0 VOLTS DC 25 DEG CELSIUS SINGLE WINDING
PURPOSE FOR WHICH DESIGNEDGENERAL
SPECIFICATION/STANDARD DATA96906-MS24141 GOVERNMENT STANDARD
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
WINDING DC RESISTANCE RATING64.5 OHMS NOMINAL SINGLE WINDING
WINDING QUANTITY1
TERMINAL TYPE AND QUANTITY8 THREADED STUD ALL FUNCTIONS
TEST DATA DOCUMENT81349-MIL-R-6106 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.).
TIME DELAY0.01 SECONDS MAXIMUM FIXED RELEASE TIME
TIME DELAY0.025 SECONDS MAXIMUM FIXED OPERATE TIME
UNTHREADED MOUNTING HOLE DIAMETER0.266 INCHES NOMINAL SINGLE MOUNTING FACILITY


Click here to Register for Free 30-day Trial