5962-01-139-1882 MICROCIRCUIT,DIGITAL Index 2540-01-139-1884 SEAT,VEHICULAR

National Stock Number:
5950-01-139-1883

Federal Supply Class:
5950

National Item Identification Number:
011391883

Description:
TRANSFORMER,POWER

Detail:
A TRANSFORMER CONSISTING OF ONE OR MORE PRIMARY WINDING(S) AND ONE OR MORE SECONDARY WINDING(S). IT MAY BE DESIGNED FOR DIRECT CONNECTION TO AN ALTERNATING CURRENT SOURCE FOR PURPOSES OF CHANGING THE SECONDARY VOLTS AND AMPERES OR DESIGNED TO ELIMINATE METALLIC INTERCONNECTION BETWEEN CIRCUITS IN AN OVERALL ONE TO ONE VOLTAGE RATIO, WITH OR WITHOUT ADDITIONAL OUTPUT WINDINGS, OR ITEMS DESIGNED TO AUTOMATICALLY MAINTAIN A CONSTANT OUTPUT VOLTAGE WITHIN SPECIFIED LIMITS UNDER VARYING INPUT OR LOAD CONDITIONS. ALSO INCLUDES ITEMS HAVING A PROVISION FOR MECHANICALLY CHANGING THE TURNS RATIO OR INDUCTIVE COUPLING IN PROGRESSIVE INCREMENTS BY MEANS OF VOLTAGE TAPS, RATIO ADJUSTER, OR DEVICES OE SIMILAR DESIGN. FOR TRANSFORMERS HAVING WINDING(S) COMMON TO BOTH INPUT AND OUTPUT CIRCUITS, SEE TRANSFORMER (1), POWER, AUTOTRANSFORMER. EXCLUDES TRANSFORMER (1), PULSE.


Manufacturer Information:
SM-A-973616-180063US ARMY COMMUNICATIONS & ELECTRONICS MATERIEL READINESS COMMAND LOGISTICS ENGINEERING DIR
TW-7122302640MAGNETIKA


Techincal Specification:
BODY HEIGHT10.750 INCHES MAXIMUM
BODY LENGTH13.500 INCHES MAXIMUM
BODY WIDTH12.870 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN MOUNTING FACILITIES PARALLEL TO LENGTH12.350 INCHES MINIMUM AND 12.410 INCHES MAXIMUM SINGLE MOUNTING FACILITY SINGLE CENTER GROUP
CENTER TO CENTER DISTANCE BETWEEN MOUNTING FACILITIES PARALLEL TO WIDTH10.230 INCHES MINIMUM AND 10.270 INCHES MAXIMUM SINGLE MOUNTING FACILITY SINGLE CENTER GROUP
FREQUENCY RATING47.0 HERTZ MINIMUM AND 63.0 HERTZ MAXIMUM SINGLE COMPONENT
INCLOSURE TYPEFULLY INCLOSED
INPUT-OUTPUT PHASE RELATIONSHIPSINGLE PHASE TO SINGLE PHASE SINGLE COMPONENT
MAXIMUM OPERATING TEMP155.0 CELSIUS
MOUNTING FACILITY QUANTITY4 SINGLE GROUP
MOUNTING HOLE DIAMETER0.430 INCHES MINIMUM AND 0.450 INCHES MAXIMUM SINGLE GROUP
MOUNTING METHODUNTHREADED HOLE SINGLE GROUP
RELIABILITY INDICATORNOT ESTABLISHED
WINDING OPERATING CURRENT104.3 AMPERES AC NOMINAL SINGLE COMPONENT SINGLE SECONDARY
WINDING FUNCTION AND QUANTITY1 PRIMARY AND 1 SECONDARY SINGLE COMPONENT
WINDING OPERATING VOLTAGE115.00 AC VOLTS NOMINAL SINGLE COMPONENT SINGLE SECONDARY
WINDING OPERATING VOLTAGE208.00 AC VOLTS NOMINAL AND 230.00 AC VOLTS NOMINAL SINGLE COMPONENT SINGLE PRIMARY
WINDING SHIELDING METHODINTERNAL SHIELD GROUNDED TO CORE AND BROUGHT OUT TO TERMINAL SINGLE COMPONENT
WINDING POWER RATING12.0 KILOVOLT-AMPERES SINGLE COMPONENT SINGLE SECONDARY
TERMINAL TYPE AND QUANTITY6 THREADED STUD