Description:
REACTOR

Detail:
A coil or coils usually constructed with cores having low magnetic reluctance, whose primary purpose is to furnish an inductive impedance in power or audio frequency circuit ranging from zero to 20 kilohertz (kilocycles). Includes audio frequency and power filter chokes, audio reactors and swinging chokes. Does not include transformers or coils used above audio frequency range. Excludes SATURABLE REACTOR. For reactors with air cores, see COIL (as modified).


Manufacturer Information:
1321-3R8-B01121ROCKWELL AUTOMATION, INC.


Techincal Specification:
CENTER TO CENTER DISTANCE BETWEEN MOUNTING FACILITIES PARALLEL TO LENGTH51.0 MILLIMETERS NOMINAL SINGLE MOUNTING FACILITY SINGLE CENTER GROUP
CENTER TO CENTER DISTANCE BETWEEN MOUNTING FACILITIES PARALLEL TO WIDTH53.0 MILLIMETERS NOMINAL SINGLE MOUNTING FACILITY SINGLE CENTER GROUP
FREQUENCY RATING50.0 HERTZ NOMINAL OR 60.0 HERTZ NOMINAL SINGLE COMPONENT
INCLOSURE TYPEOPEN
INDUCTANCE RATING3.00 MICROHENRIES NOMINAL SINGLE COMPONENT SINGLE WINDING
INDUCTANCE TYPEFIXED
OVERALL HEIGHT127.0 MILLIMETERS NOMINAL
OVERALL LENGTH152.0 MILLIMETERS NOMINAL
OVERALL WIDTH76.0 MILLIMETERS NOMINAL
MOUNTING FACILITY QUANTITY4 SINGLE GROUP
MOUNTING METHODSLOT SINGLE GROUP
SPECIAL FEATURESAMBIENT TEMP. 0 DEG C TO +60 DEG C; MAX VOLTAGE: 600 VAC; IRON CORE, 3% OR 5% IMPEDANCE BASED ON FUNDAMENTAL CURRENT RATINGS
RATING METHODELECTRICAL SINGLE COMPONENT SINGLE WINDING
RELIABILITY INDICATORNOT ESTABLISHED
WINDING OPERATING CURRENT8.0 AMPERES AC MINIMUM AND 12.0 AMPERES AC MAXIMUM SINGLE COMPONENT SINGLE SECONDARY
WINDING QUANTITY3 SINGLE COMPONENT
TERMINAL TYPE AND QUANTITY1 TERMINAL BLOCK W/SCREWS