ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE TWO |
AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 PUSH BUTTON |
OVERALL HEIGHT | 1.770 INCHES MAXIMUM |
OVERALL LENGTH | 2.170 INCHES NOMINAL |
OVERALL WIDTH | 2.000 INCHES NOMINAL |
MATERIAL | PLASTIC CASE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 5.0 AMPERES AC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
POLE QUANTITY | 3 |
RESET METHOD | MANUAL |
SWITCH CURRENT RATING AND TYPE IN AMPS | 5.0 AC |
SWITCH LOCATION AND POSITION DESIGNATION | EXTERNAL AT POLE ONE |
SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC |
TERMINAL TYPE AND QUANTITY | 6 TAB, SOLDER LUG |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.500 MINIMUM AT 200 PCT AND 9.000 MAXIMUM AT 200 PCT AND 0.070 MINIMUM AT 300 PCT AND 0.300 MAXIMUM AT 300 PCT AND 0.009 MINIMUM AT 500 PCT AND 0.0900 MAXIMUM AT 500 PCT ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
ULTIMATE TRIP TIME PER POLE IN SECONDS | 2.000 MINIMUM AND 60.000 MAXIMUM ALL LOCATIONS |