ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE ONE |
BODY LENGTH | 1.562 INCHES MAXIMUM |
BODY STYLE | SINGLE POLE TYPE |
BODY WIDTH | 0.621 INCHES MAXIMUM |
BUSHING LENGTH | 0.375 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.875 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
FREQUENCY IN HERTZ | 400.0 SINGLE LOCATION |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | EXPLOSION PROOF AND FUNGUS RESISTANT AND MOISTURE RESISTANT |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 1.0 AMPERES AC SINGLE LOCATION |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 300.0 AC SINGLE LOCATION |
MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING W/PANEL SEAL |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.700 INCHES MAXIMUM |
NOMINAL THREAD SIZE | 0.375 INCHES |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC SINGLE LOCATION |
POLE QUANTITY | 1 |
RESET METHOD | MANUAL |
TERMINAL TYPE AND QUANTITY | 2 WIRE HOOK |
THREAD QUANTITY PER INCH | 32 |
THREAD SERIES DESIGNATOR | UNEF |
TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.150 MINIMUM AT 200 PCT AND 4.000 MAXIMUM AT 200 PCT AND 0.030 MINIMUM AT 300 PCT AND 0.900 MAXIMUM AT 300 PCT AND 0.006 MINIMUM AT 500 PCT AND 0.030 MAXIMUM AT 500 PCT SINGLE LOCATION |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
ULTIMATE TRIP TIME PER POLE IN SECONDS | 30.000 MAXIMUM SINGLE LOCATION |